F-CIM 89
LOGICAL OR
REUSABLE
Function:
IF (S
n-1
1 or A 1)
S
n
= 1.0
ELSE
S
n
= 0.0
Description:
This module produces an output of 1.0 if either or both of the A and X inputs have values that are
greater than or equal to 1.0. The A input can be any L,B,C [S], or H type data.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-33